Alarms people still believe.

Why machine alarms chatter on and off around a limit, and the two settings that stop it: a hold time before an alarm raises and a deadband before it clears. With a worked example, what to do when a warning turns critical, and why a machine that stops reporting must not clear its alarms.

2 min read · Updated 24 November 2026

Why alarms chatter

A bearing that runs at 79 to 81 °C against an 80 °C limit will cross the limit dozens of times an hour. A plain “above the limit” check raises an alarm on every crossing and clears it on every dip. The screen flickers, the inbox fills, and within a week people stop looking. The alarm that matters then arrives in a list nobody reads.

The fix is not a higher limit. It is two small rules on when an alarm may start and when it may stop.

Hold time: the condition must last

Before an alarm raises, the reading must stay past its limit for a set time (the hold time, also called an on-delay). A single spike from a noisy sensor or a motor starting up passes and never raises anything. A real rise stays, and raises a few seconds later.

Keep the hold short: seconds, not minutes. Its job is to ignore spikes, not to hide a fault. Stamp the alarm with the time the condition was first seen, not the end of the hold, so the record shows when the trouble started.

Deadband: the reading must come back clearly

An alarm should not clear the moment the reading dips under its limit. Require it to come back past the limit by a margin first (the deadband, or hysteresis). A reading that hovers on the line then stays one alarm instead of fifty.

An example: a bearing temperature limit of 80 °C with a 5 % deadband (4 °C)
ReadingAlarm
Rises to 80.5 °C, then 79 °C after 2 sNothing: it did not hold
Stays above 80 °C for more than the hold timeRaises
Falls to 79 °CStays active: still within 4 °C of the limit
Falls to 75.5 °CClears: past the limit by more than the deadband

When a warning turns critical

Most signals have two limits: a warning and a critical one. When a warning that someone has already acknowledged goes critical, treat it as new: drop the acknowledgement so it has to be seen again. The same hold time applies to the step up, so a spike over the critical limit does not escalate it.

Silence is not healthy

When a sensor or a gateway stops reporting, its last reading freezes. If the alarm logic reads silence as normal, open alarms clear themselves and new ones can never raise. Suspend the alarms of a machine you cannot observe (no data, gateway offline, or locked out for maintenance): they neither raise nor clear until readings come back, and the missing data is shown as missing.

How Atlas Edge does it

Atlas Edge evaluates alarms on the server as readings arrive. A condition must hold before it raises or escalates, and an alarm clears only once the reading is clearly back inside its limit. A warning that turns critical becomes unacknowledged again. Machines that are locked out, behind an offline gateway or not reporting yet are suspended: their alarms neither raise nor clear. Every alarm is kept in a journal with when it was raised, acknowledged and cleared, critical ones are emailed to the people who can act on them, and a critical alarm still unacknowledged after a set time sends a reminder.

Guide

Quick answers.

What is alarm chattering?

An alarm that raises and clears again and again in a short time, usually because a reading sits close to its limit or the sensor is noisy. It trains people to ignore alarms. A hold time before raising and a deadband before clearing stop it.

How big should the deadband be?

Big enough to cover the normal ripple of the reading, small enough that a real recovery clears the alarm. A few per cent of the limit suits most temperatures and vibration levels; look at a day of the signal's history and set it just above its usual ripple.

Does a hold time delay real alarms?

By the length of the hold, so keep it to seconds. Machine faults that alarms catch, a bearing heating or vibration rising, develop over minutes or longer, so a few seconds cost nothing and remove the spikes.