Why alarms chatter
A bearing that runs at 79 to 81 °C against an 80 °C limit will cross the limit dozens of times an hour. A plain “above the limit” check raises an alarm on every crossing and clears it on every dip. The screen flickers, the inbox fills, and within a week people stop looking. The alarm that matters then arrives in a list nobody reads.
The fix is not a higher limit. It is two small rules on when an alarm may start and when it may stop.
Hold time: the condition must last
Before an alarm raises, the reading must stay past its limit for a set time (the hold time, also called an on-delay). A single spike from a noisy sensor or a motor starting up passes and never raises anything. A real rise stays, and raises a few seconds later.
Keep the hold short: seconds, not minutes. Its job is to ignore spikes, not to hide a fault. Stamp the alarm with the time the condition was first seen, not the end of the hold, so the record shows when the trouble started.
Deadband: the reading must come back clearly
An alarm should not clear the moment the reading dips under its limit. Require it to come back past the limit by a margin first (the deadband, or hysteresis). A reading that hovers on the line then stays one alarm instead of fifty.
| Reading | Alarm |
|---|---|
| Rises to 80.5 °C, then 79 °C after 2 s | Nothing: it did not hold |
| Stays above 80 °C for more than the hold time | Raises |
| Falls to 79 °C | Stays active: still within 4 °C of the limit |
| Falls to 75.5 °C | Clears: past the limit by more than the deadband |
When a warning turns critical
Most signals have two limits: a warning and a critical one. When a warning that someone has already acknowledged goes critical, treat it as new: drop the acknowledgement so it has to be seen again. The same hold time applies to the step up, so a spike over the critical limit does not escalate it.
Silence is not healthy
When a sensor or a gateway stops reporting, its last reading freezes. If the alarm logic reads silence as normal, open alarms clear themselves and new ones can never raise. Suspend the alarms of a machine you cannot observe (no data, gateway offline, or locked out for maintenance): they neither raise nor clear until readings come back, and the missing data is shown as missing.
How Atlas Edge does it
Atlas Edge evaluates alarms on the server as readings arrive. A condition must hold before it raises or escalates, and an alarm clears only once the reading is clearly back inside its limit. A warning that turns critical becomes unacknowledged again. Machines that are locked out, behind an offline gateway or not reporting yet are suspended: their alarms neither raise nor clear. Every alarm is kept in a journal with when it was raised, acknowledged and cleared, critical ones are emailed to the people who can act on them, and a critical alarm still unacknowledged after a set time sends a reminder.